Final | 6/3/2015 | 6/4/2015 | 6/4/2015 | A | PASS |
Eric Story
|
|
|
Go through gate, man door is open Phone #: ###-#### Inspection requested via web by Eric Schroeder final ok
|
Final | 5/27/2015 | 5/28/2015 | 5/28/2015 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Eric Schroeder NEC 300.5 Underground conduit depth at 13 " Circuit shall have GFCI protection at soure
|
Electrical Rough-In | 5/14/2015 | 5/14/2015 | 5/14/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Eric Schroeder Undergound conduit depth at 13", circuits shall have GFCI protection at source. Detached garage rough in ok cover
|
Electrical Rough-In | 5/13/2015 | 5/14/2015 | 5/14/2015 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Eric Schroeder Verify trench depth, NEC 210.52(G)(1) Branch circuit suppling receptacle shall not supply outlets outside of the garage
|
Issue PAID IN FULL permit | | | 5/13/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/13/2015 | | DONE |
|
|
|
This permit was created on the web by Eric Schroeder
|