Final | 7/16/2015 | 7/16/2015 | 7/16/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Final ok
|
Final | 7/13/2015 | 7/14/2015 | 7/14/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 110.3(B)- Light fixture over entry shall be installed to manufacturers listing. Fixture upside down. 210.52(C)(1)- Receptacle outlet shall be located with in 24 inches of edge of sink. 410.16(C)- Luminaire shall have 12 inches clearance from shelf in laundry closet.
|
Permanent Service | 6/4/2015 | 6/4/2015 | 6/4/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov p/s u/g n ok
|
Electrical Rough-In | 5/20/2015 | 5/20/2015 | 5/20/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover
|
Electrical Rough-In | 5/19/2015 | 5/19/2015 | 5/19/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 300.4 NM cable ran through bored hole that does not maitain 1 1/4 in shall be protected from physical damage by nail plates 334.30 NM cable shall be secured with 12in of boxes A/C stub NM cables shall not be stapled on edge
|
Issue PAID IN FULL permit | | | 5/18/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/15/2015 | | DONE |
|
|
|
This permit was created on the web by daniel bibikov
|
First Notice | 7/16/2015 | 7/16/2015 | | | |
Rock A. Hudson
|
|
|
|