First Notice | 6/25/2015 | 6/25/2015 | 9/23/2015 | | DONE |
Daryl DeGrange
|
|
|
|
Final | 6/25/2015 | 6/25/2015 | 6/25/2015 | P | PASS |
Daryl DeGrange
|
|
|
would like call ahead; Scott Phone #: ###-#### final ok
|
Electrical Rough-In | 6/19/2015 | 6/19/2015 | 6/19/2015 | P | PASS |
Rock A. Hudson
|
|
|
ceiling; Scott Phone #: ###-#### Grid rough in ok cover
|
Electrical Rough-In | 6/18/2015 | 6/18/2015 | 6/18/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Overhead, above ceiling - Scott Phone #: ###-#### 4-05-32- Code violation not to be retained. 300.11- Ceiling grid shall not support low volt wiring. Existing low volt wiring shall be removed or supported indepandant of grid.
|
Electrical Rough-In | 6/2/2015 | 6/2/2015 | 6/3/2015 | P | PASS |
Rock A. Hudson
|
|
|
Scott Phone #: ###-#### Wall rough in ok cover
|
Issue PAID IN FULL permit | | | 5/22/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/22/2015 | | DONE |
|
|
|
This permit was created on the web by Todd Sellman
|