Permit Information
Permit NumberELE15-01541
StatusFinaled
Name HIGH COUNTRY ELECTRIC
Site Address 999 W MAIN ST
Project Name 
Customer Number15074
ePlanReviewNo
Description
Alteration: install and demo electric per plans
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/22/20156/23/20156/23/2015APASS
DetailsRex Boyles
call ###-#### before going to site to unlock the room or call me ###-#### Phone #: ###-#### Inspection requested via web by Karl Paige corrections made final ok
Final6/16/20156/16/20156/16/2015PFAIL
DetailsDaryl DeGrange
Phone #: ###-#### Inspection requested via web by Karl Paige Not all luminaires have support wires at opposing corners. NEC 300.11 Fixture whips shall be supported off ceiling grid. NEC 348.30 FMC metal raceways shall be supported NE 800.25 Shall remove all abandoned cables and conduit
Electrical Rough-In5/27/20155/27/20155/27/2015PPASS
DetailsDaryl DeGrange
project located on 9th floor south out of elevator take a left to the east at the end of hallway turn north through door room on your right Phone #: ###-#### Inspection requested via web by Karl Paige rough-in ok cover walls
Issue PAID IN FULL permit  5/27/2015 DONE
Payment received via Govolutions
Application received  5/27/2015 DONE
This permit was created on the web by Karl Paige
First Notice6/23/20156/23/2015   
DetailsRex Boyles