Final | 6/3/2015 | 6/3/2015 | 6/3/2015 | A | PASS |
Rex Boyles
|
|
|
Call for access code Range is factory hard wired without a ground, A/C is a in house unit so the extras wire in conduit runs to a branch circuit in the living room. Phone #: ###-#### Inspection requested via web by David Nelson UNIT 3 corrections made final ok
|
Final | 6/3/2015 | 6/3/2015 | 6/3/2015 | A | CANC |
Rex Boyles
|
|
|
Call for access code Phone #: ###-#### >> Inspection requested via web by David Nelson Inspection cancelled from web by: David Nelson
|
Rough-In Permanent Service | 6/1/2015 | 6/2/2015 | 6/2/2015 | A | CANC |
Rex Boyles
|
|
|
UNIT #3, replace panel due to flooding Phone #: ###-#### Inspection requested via web by David Nelson needed r/i only
|
Electrical Rough-In | 6/2/2015 | 6/2/2015 | 6/2/2015 | P | FAIL |
Rex Boyles
|
|
|
UNIT #3, replace panel due to flooding Phone #: ###-#### Inspection requested via web by David Nelson multiwire branch circuits need 2 pole breaker, tighten locknuts on conduits and install reducing washers where needed, some conduits with no ground conductor also need locknut tightened, conduit with 3 current carrying conductors have only 1 nuetral conductor for 1 phase system, strap conduits entering panel, install AFCI protection for bdrm. if possible, change range receptacle to 4 wire fed from sub panel
|
Issue PAID IN FULL permit | | | 6/1/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/1/2015 | | DONE |
|
|
|
This permit was created on the web by David Nelson
|
First Notice | 6/3/2015 | 6/3/2015 | | | |
Rex Boyles
|
|
|
|