Final | 6/9/2015 | 6/9/2015 | 6/9/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by cory carman Final ok
|
Electrical Rough-In | 6/3/2015 | 6/3/2015 | 6/3/2015 | P | PASS |
Rock A. Hudson
|
|
|
Under ground rough ok. To verify lperimeter bond distance and receptacle location by pool
|
Final | 6/3/2015 | 6/3/2015 | 6/3/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Fiberglass pool with a 12volt light Phone #: ###-#### Inspection requested via web by cory carman 680.22(A)(1)- At least one receptacle 15 or 20 amp 120 volt GFCI outlet shall be located between 6' and 20' of inside wall of pool. 680.26( B)(2)- Perimeter surface #8 conductor shall be located within 18" to 24" of edge of pool and shall be 4" to 6" below grade. 200.6- Grounded conductor shall be identified full length for conductors smaller than #6.
|
Issue PAID IN FULL permit | | | 6/3/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/3/2015 | | DONE |
|
|
|
This permit was created on the web by cory carman
|