Final | 7/22/2015 | 7/23/2015 | 7/23/2015 | P | PASS |
Rex Boyles
|
|
|
Final Reinspection please. Phone #: ###-#### Inspection requested via web by Paula Gratiot correction made final ok
|
Final | 7/22/2015 | 7/22/2015 | 7/22/2015 | P | FAIL |
Eric Story
|
|
|
Homeowners will be on site. Phone #: ###-#### Inspection requested via web by Paula Gratiot 210.12 (a) arc fault protection for required for bedrooms
|
Final | 7/6/2015 | 7/7/2015 | 7/7/2015 | A | CANC |
Rock A. Hudson
|
|
|
Floor heat only please.... Inspection requested via web by Paula Gratiot needed rough in inspection
|
Electrical Rough-In | 7/7/2015 | 7/7/2015 | 7/7/2015 | P | PASS |
Rock A. Hudson
|
|
|
Floor heat only please.... Inspection requested via web by Paula Gratiot floor heat rough in ok cover
|
Electrical Rough-In | 7/2/2015 | 7/6/2015 | 7/6/2015 | A | FAIL |
Rock A. Hudson
|
|
|
This is a floor heat circuit inspection only. Homeowners will be on site. Thanks. Phone #: ###-#### Inspection requested via web by Paula Gratiot 110.3- As per manufacturers instructions cold lead splice, heat cable end and sensor shall be recessed in sub floor.
|
Electrical Rough-In | 6/8/2015 | 6/9/2015 | 6/9/2015 | A | PASS |
Eric Story
|
|
|
Homeowners will be present to unlock. Jeff McGilvery is contractor at ###-#### Phone #: ###-#### Inspection requested via web by Paula Gratiot rough-in back bed and bath ok cover
|
Issue PAID IN FULL permit | | | 6/8/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/8/2015 | | DONE |
|
|
|
This permit was created on the web by Paula Gratiot
|