Final | 8/13/2015 | 8/14/2015 | 8/14/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Final ok
|
Final | 8/13/2015 | 8/13/2015 | 8/13/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 210.8- GFCI not working in space 100, unable to test. 408.4- label house panel and check labels in rest 101 dryer and above.
|
Permanent Service | 6/15/2015 | 6/15/2015 | 6/15/2015 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov p/s u/g n ok
|
Electrical Rough-In | 6/11/2015 | 6/11/2015 | 6/11/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover
|
Final | 6/11/2015 | 6/11/2015 | 6/11/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover
|
Change Status to I | | | 6/11/2015 | | DONE |
|
|
|
was finaled by mistake
|
Electrical Rough-In | 6/10/2015 | 6/10/2015 | 6/10/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Inspection requested via web by daniel bibikov 250.24(A)(5)- Grounded conductor shall not be connected to non current carrying metal parts on load side of service disconnecting means. remove bonding screw in panel lower left unit. 300.4- NM cable shall be protected from physical damage when ran through bored holes that do not maintain 1 1/4" from framing surface. 45 degree drill corners, upper plates shallow or angled holes. * no contact information provided.
|
Issue PAID IN FULL permit | | | 6/10/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/10/2015 | | DONE |
|
|
|
This permit was created on the web by daniel bibikov
|
First Notice | 8/14/2015 | 8/14/2015 | | | |
Rock A. Hudson
|
|
|
|