Final | 9/16/2015 | 9/17/2015 | 9/17/2015 | A | PASS |
Rex Boyles
|
|
|
Dan garage code- 1234 Phone #: ###-#### Inspection requested via web by Dan Hobdey final ok
|
Rough-In Permanent Service | 6/17/2015 | 6/17/2015 | 6/17/2015 | P | PASS |
Eric Story
|
|
|
Inspection requested via web by Dan Hobdey rough-in ok p/s u/g n ok
|
Rough-In Permanent Service | 6/16/2015 | 6/16/2015 | 6/16/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Dan Phone #: ###-#### Inspection requested via web by Dan Hobdey 300.4- NM cable shall not be installed where it may be subject to physical damage. 334.30- MN cable shall be supported every 4 1/2' minimum. Fr. bed, furnace wire. 334.80- Where 2 or more NM cables ran through bored holes without maintaining spacing derating calculations shall apply. BCC- Firewalls shall be clear for fire barrier. Wiring shall be relocated from behind studs in firewalls in master bed and garage.
|
Issue PAID IN FULL permit | | | 6/16/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/16/2015 | | DONE |
|
|
|
This permit was created on the web by Dan Hobdey
|