Final | 9/15/2015 | 9/16/2015 | 9/16/2015 | A | PASS |
Rock A. Hudson
|
|
|
Dan Phone #: ###-#### Inspection requested via web by Dan Hobdey Final ok
|
Final | 9/14/2015 | 9/15/2015 | 9/15/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Dan Garage code- 1234 Phone #: ###-#### Inspection requested via web by Dan Hobdey 210.23(A)(2)- Vac system fastened in place exceeds 50 percent of branch circuit in garage so dedicated ciruit required. 210.52- Any wall space 24" or wider shall have a receptacle outlet. 230.70(B)- Each service disconnnect shall be permanently marked to identify it as a service disconnect. 410.10(D)- Recessed can trim main bath over threshold of tub shower shall be listed for damp locations.
|
Rough-In Permanent Service | 6/17/2015 | 6/17/2015 | 6/17/2015 | P | PASS |
Eric Story
|
|
|
Inspection requested via web by Dan Hobdey rough-in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 6/16/2015 | 6/16/2015 | 6/16/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Dan Phone #: ###-#### Inspection requested via web by Dan Hobdey 300.4- NM calbe shall not be ran where it may be subject to physical damage. master bed firewall on clips. 334.30- NM cable shall be secured within 12" of smoke in masteer bed. 334.80- Where 2 or more NM cables are ran through bored holes without maintaining spacing derating calculations shall apply. BCC- Firewall shall be clear for fire barrier. Wiring shall be relocated from behind studs in firewalls in master bed and garage.
|
Issue PAID IN FULL permit | | | 6/16/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/16/2015 | | DONE |
|
|
|
This permit was created on the web by Dan Hobdey
|