Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberELE15-01811
StatusFinaled
Name STEVEN RAMAEKERS
Site Address 4319 E AMITY RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Interior remodel for new bed & bath
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/5/201511/6/201511/6/2015APASS
DetailsRex Boyles
Lacey Phone #: ###-#### corrections made final ok
Final10/21/201510/23/201510/23/2015AFAIL
DetailsEric Story
Steve Phone #: ###-#### 210.8 all receptacles located in a bathroom shall have GFCI protection 410.16 (a) fixtures located in a closet shall be completely enclosed
Electrical Rough-In7/23/20157/24/20157/24/2015APASS
DetailsBob Reichert
Lacey Phone #: ###-#### corrections made, powder room and bath ok cover
Electrical Rough-In7/21/20157/21/20157/21/2015PFAIL
DetailsBob Reichert
Lacey Phone #: ###-#### called owner, left correction notice, NEC 334.30 nm cable shall be secured within 12" of box, 300.4 edge of bored hole shall be 1 1/4" from edge of framing member, 110.3(B) shall install equipment per manufacturer instructions ( ground ferrules ), BCC all make-up shall be done, shall not install panel in clothes closet, see NEC240.24D
Conference6/18/20156/19/20156/19/2015ADONE
DetailsBob Reichert
Steve Phone #: ###-#### talked about wiring bath, bedroom
Application received  6/16/2015  
Issue PAID IN FULL permit  6/16/2015 DONE
DetailsChristina Prado