Final | 11/5/2015 | 11/6/2015 | 11/6/2015 | A | PASS |
Rex Boyles
|
|
|
Lacey Phone #: ###-#### corrections made final ok
|
Final | 10/21/2015 | 10/23/2015 | 10/23/2015 | A | FAIL |
Eric Story
|
|
|
Steve Phone #: ###-#### 210.8 all receptacles located in a bathroom shall have GFCI protection 410.16 (a) fixtures located in a closet shall be completely enclosed
|
Electrical Rough-In | 7/23/2015 | 7/24/2015 | 7/24/2015 | A | PASS |
Bob Reichert
|
|
|
Lacey Phone #: ###-#### corrections made, powder room and bath ok cover
|
Electrical Rough-In | 7/21/2015 | 7/21/2015 | 7/21/2015 | P | FAIL |
Bob Reichert
|
|
|
Lacey Phone #: ###-#### called owner, left correction notice, NEC 334.30 nm cable shall be secured within 12" of box, 300.4 edge of bored hole shall be 1 1/4" from edge of framing member, 110.3(B) shall install equipment per manufacturer instructions ( ground ferrules ), BCC all make-up shall be done, shall not install panel in clothes closet, see NEC240.24D
|
Conference | 6/18/2015 | 6/19/2015 | 6/19/2015 | A | DONE |
Bob Reichert
|
|
|
Steve Phone #: ###-#### talked about wiring bath, bedroom
|
Application received | | | 6/16/2015 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 6/16/2015 | | DONE |
Christina Prado
|
|
|
|