Final | 10/14/2015 | 10/15/2015 | 10/15/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Steve Craig Final ok
|
Final | 10/5/2015 | 10/6/2015 | 10/6/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Inspection requested via web by Steve Craig 400.8- Wiring for split system. Flexible cords shall not be ran through walls or installed in a wall. 406.12- All 15 and 20 amp 120 volt receptacle outlets installed in a dwelling shall be tamper resistant type. Kit GFI and washer. 422.30- A disconnecting means shall be provided with in sight of water heater. 110.25- lock out acceptable. No contact information provided
|
Electrical Rough-In | 6/24/2015 | 6/25/2015 | 6/25/2015 | A | PASS |
Daryl DeGrange
|
|
|
Room to be remodeled and rewired is under a different permit. There are 2 permits for this job. Please call Steve at ###-#### with h questions Phone #: ###-#### Inspection requested via web by Steve Craig correction done, rough-in ok cover
|
Electrical Rough-In | 6/17/2015 | 6/18/2015 | 6/18/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection request via web by Steve Craig 300.4- NM cable shall be protected from physical damage where ran thru notched or bored holes that do not maintain 1 1/4" from framing surface. 725.136- Low volt wiring for chime shall not accupy same box as power wiring. Complete equipment grounding for sub panel. Room between apartment and house not wired. #2 Ser ran to sub panel check overcurrent. Addition to 2109
|
Issue PAID IN FULL permit | | | 6/17/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/17/2015 | | DONE |
|
|
|
This permit was created on the web by Steve Craig
|