First Notice | 10/7/2015 | 10/7/2015 | 1/5/2016 | | DONE |
Rock A. Hudson
|
|
|
|
Final | 10/6/2015 | 10/7/2015 | 10/7/2015 | A | PASS |
Rock A. Hudson
|
|
|
Mark Phone #: ###-#### Final ok
|
Final | 9/22/2015 | 9/23/2015 | 9/23/2015 | A | PART |
Rock A. Hudson
|
|
|
Mark-wants Temp CO Phone #: ###-#### North side ventalation provided, south not ventalated. All electrical located above classified areas. Need finish sign and pour seal offs for paint booth. Temp final ok
|
Final | 9/16/2015 | 9/17/2015 | 9/17/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Mark Phone #: ###-#### 511.3- If ventalationnot provided all electrical below 18" shall be removed or relocated above classified area. Doorways into offices areas in violation. If ventalation provided all areas ok at present location. 511.12- All 15 and 20 amp 120 volt receptacle outlets shall have GFCI protection. 314.29- Boxes located behind paint booth are not accessible they shall be eliminated.
|
Electrical Rough-In | 9/17/2015 | 9/17/2015 | 9/17/2015 | P | PART |
Rock A. Hudson
|
|
|
Mark Phone #: ###-#### Paint booth rough in ok
|
Issue PAID IN FULL permit | | | 9/7/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 6/23/2015 | | |
|
|
|
|
Application received | | | 6/23/2015 | | DONE |
|
|
|
This permit was created on the web by Mark Morgan
|