Final | 2/8/2016 | 2/8/2016 | 2/8/2016 | P | PASS |
Rex Boyles
|
|
|
final out powerbound electric's permit as per Sublime electric. new permit by Sublime to finish ele15-01904 final ok
|
Permanent Service | 7/15/2015 | 7/15/2015 | 7/15/2015 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by steve cooper p/s u/g n ok
|
Rough-In Permanent Service | 6/24/2015 | 6/25/2015 | 6/25/2015 | A | CANC |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by steve cooper needed r/i only
|
Electrical Rough-In | 6/25/2015 | 6/25/2015 | 6/25/2015 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by steve cooper corrections made r/i ok
|
Rough-In Permanent Service | 6/24/2015 | 6/24/2015 | 6/24/2015 | P | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by steve cooper 210.52(D)-in dwelling units at least one receptacle shall be installed in bathrooms within 3 foot of each basin. 300.4-not less than 11/4" from bored holes to edge of stud.
|
Issue PAID IN FULL permit | | | 6/24/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/24/2015 | | DONE |
|
|
|
This permit was created on the web by steve cooper
|