Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE15-02027
StatusFinaled
Name SZURGOT ELECTRIC
Site Address 203 W MAIN ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Install redundant grounded outlets in exam rooms and wire transformer and phase convertor for elevator.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Print Statement  4/14/2016 DONE
stamped past due
First Notice10/29/201510/29/20153/22/2016 DONE
DetailsRex Boyles
This permit finaled on the web by Barbara Szurgot
Print Statement  12/22/2015 DONE
Print Statement  12/22/2015 DONE
Final10/28/201510/29/201510/29/2015APASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by Barbara Szurgot final ok including elevator final
Final10/8/201510/8/201510/8/2015PPART
DetailsRex Boyles
GFCIs repaired Phone #: ###-#### Inspection requested via web by Barbara Szurgot corrections made final ok BUT haven't done any elevator inspections yet
Final9/30/201510/1/201510/1/2015AFAIL
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by Barbara Szurgot 210.8 B2- GFCI protection required within 6' of sink in other than dwellings upst. breakroom and dnst. lab draw area. 210.8B1-GFCI protection required in bathrooms(dnst. gfi not functioning. 110.16-arc flash hazard warning labels on loadcenters. Need to see elevator pit electrical at final inspection, unless done by elevator inspector.
Final8/7/20158/7/20158/7/2015PPART
DetailsRex Boyles
Elevator portion not done yet, but they need temp occupancy for opening. Please call Steve with any questions, ###-#### Phone #: ###-#### Inspection requested via web by Barbara Szurgot partial final for 4 exam rooms dnst. Note:GFCI required within 6 foot of sink rear exam room. Temporary occupancy ok for these 4 rooms only
Electrical Rough-In7/18/20157/20/20157/20/2015APASS
DetailsRex Boyles
Please call Steve with any questions on inspection. Phone #: ###-#### Inspection requested via web by Barbara Szurgot 1st and 2nd flr elevator lobby walls and ceilings r/i ok
Electrical Rough-In7/7/20157/8/20157/8/2015APASS
DetailsRex Boyles
Wall inspection Phone #: ###-#### Inspection requested via web by Barbara Szurgot r/i ok upst. and dnst. Steve says whole house is conduit. Will satisfy patient care codes with additional ground wire where needed. (except elevator)
Issue PAID IN FULL permit  7/2/2015 DONE
Payment received via Govolutions
Application received  7/2/2015 DONE
This permit was created on the web by Barbara Szurgot