Print Statement | | | 4/14/2016 | | DONE |
|
|
|
stamped past due
|
First Notice | 10/29/2015 | 10/29/2015 | 3/22/2016 | | DONE |
Rex Boyles
|
|
|
This permit finaled on the web by Barbara Szurgot
|
Print Statement | | | 12/22/2015 | | DONE |
|
|
|
|
Print Statement | | | 12/22/2015 | | DONE |
|
|
|
|
Final | 10/28/2015 | 10/29/2015 | 10/29/2015 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot final ok including elevator final
|
Final | 10/8/2015 | 10/8/2015 | 10/8/2015 | P | PART |
Rex Boyles
|
|
|
GFCIs repaired Phone #: ###-#### Inspection requested via web by Barbara Szurgot corrections made final ok BUT haven't done any elevator inspections yet
|
Final | 9/30/2015 | 10/1/2015 | 10/1/2015 | A | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot 210.8 B2- GFCI protection required within 6' of sink in other than dwellings upst. breakroom and dnst. lab draw area. 210.8B1-GFCI protection required in bathrooms(dnst. gfi not functioning. 110.16-arc flash hazard warning labels on loadcenters. Need to see elevator pit electrical at final inspection, unless done by elevator inspector.
|
Final | 8/7/2015 | 8/7/2015 | 8/7/2015 | P | PART |
Rex Boyles
|
|
|
Elevator portion not done yet, but they need temp occupancy for opening. Please call Steve with any questions, ###-#### Phone #: ###-#### Inspection requested via web by Barbara Szurgot partial final for 4 exam rooms dnst. Note:GFCI required within 6 foot of sink rear exam room. Temporary occupancy ok for these 4 rooms only
|
Electrical Rough-In | 7/18/2015 | 7/20/2015 | 7/20/2015 | A | PASS |
Rex Boyles
|
|
|
Please call Steve with any questions on inspection. Phone #: ###-#### Inspection requested via web by Barbara Szurgot 1st and 2nd flr elevator lobby walls and ceilings r/i ok
|
Electrical Rough-In | 7/7/2015 | 7/8/2015 | 7/8/2015 | A | PASS |
Rex Boyles
|
|
|
Wall inspection Phone #: ###-#### Inspection requested via web by Barbara Szurgot r/i ok upst. and dnst. Steve says whole house is conduit. Will satisfy patient care codes with additional ground wire where needed. (except elevator)
|
Issue PAID IN FULL permit | | | 7/2/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/2/2015 | | DONE |
|
|
|
This permit was created on the web by Barbara Szurgot
|