Final | 9/22/2015 | 9/23/2015 | 9/23/2015 | A | PASS |
Rock A. Hudson
|
|
|
Roger Phone #: ###-#### Final ok
|
Final | 9/21/2015 | 9/22/2015 | 9/22/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Call for access code - Roger Phone #: ###-#### 210.8(B)(5)- All 120 volt 15 and 20 amp receptacle outlets installed within 6' of a sink shall have GFCI protection.
|
Permanent Service | 9/10/2015 | 9/11/2015 | 9/11/2015 | A | PASS |
Rock A. Hudson
|
|
|
Roger Phone #: ###-#### p/s u/g n ok
|
Electrical Rough-In | 9/11/2015 | 9/11/2015 | 9/11/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Roger Phone #: ###-#### 110.14- Terminals for conductors shall be identified for finely stranded wire. Stranded wire connections shall have connectors that involve all strands of a conductor to be involved in connection.
|
Electrical Rough-In | 7/13/2015 | 7/14/2015 | 7/14/2015 | A | PASS |
Rock A. Hudson
|
|
|
Roger- Phone #: ###-#### rough in ok cover
|
Application received | | | 7/2/2015 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 7/2/2015 | | DONE |
|
|
|
|
First Notice | 9/23/2015 | 9/23/2015 | | | |
Rock A. Hudson
|
|
|
|