Final | 9/13/2015 | 9/14/2015 | 9/14/2015 | A | PASS |
Rex Boyles
|
|
|
Dan Phone #: ###-#### Inspection requested via web by Dan Hobdey final ok
|
Permanent Service | 7/7/2015 | 7/7/2015 | 7/7/2015 | P | PASS |
Rock A. Hudson
|
|
|
ok to cover // Dan Phone #: ###-#### Under ground conduit not connected to conduit below meter base. p/s u/g n ok
|
Electrical Rough-In | 7/7/2015 | 7/7/2015 | 7/7/2015 | P | PASS |
Rock A. Hudson
|
|
|
ok to cover // Dan Phone #: ###-#### Rough in ok cover
|
Rough-In Permanent Service | 7/3/2015 | 7/6/2015 | 7/6/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Dan Phone #: ###-#### Inspection requested via web by Dan Hobdey 110.11- Concrete encased rebar exposed to weather outdoors will rust. Ground rods shall be added or rebar shall be located in wall. 300.4- NM cable where enters fireplace shall have bushing. 300.4- NM cable shall be protected from physical damage where ran through bored holes that do not maintain 1 1/4" from framing surface. 45 degree corners.
|
Issue PAID IN FULL permit | | | 7/3/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/3/2015 | | DONE |
|
|
|
This permit was created on the web by Dan Hobdey
|