Final | 7/10/2015 | 7/10/2015 | 7/10/2015 | P | PASS |
Rock A. Hudson
|
|
|
would like call ahead; Mike Phone #: ###-#### Final ok
|
Electrical Rough-In | 7/5/2015 | 7/6/2015 | 7/6/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Please call 30 minutes advance notice ###-#### Thanks, Mike Inspection requested via web by Mike Swift Horzontal NM cable shall be protected from physical damage below 8'. 230.79- Minimum feeders- more than 2 circuits shall be 60 amp minimum or reduce number of circuits to 2 and 30 disconnect. 210.8- Outdoor work shed all 120 volt 15 or 20 amp receptacle outlets shall have GFCI protection Verbal correction with contractor on site
|
Issue PAID IN FULL permit | | | 7/5/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/5/2015 | | DONE |
|
|
|
This permit was created on the web by Mike Swift
|