Final | 7/9/2015 | 7/9/2015 | 7/9/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Final ok
|
Electrical Rough-In | 7/9/2015 | 7/9/2015 | 7/9/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Corrections made. Rough in ok
|
Final | 7/7/2015 | 7/7/2015 | 7/7/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Please call for access Phone #: ###-#### Inspection requested via web by kendall bender See rough in
|
Electrical Rough-In | 7/7/2015 | 7/7/2015 | 7/7/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Please call for access Phone #: ###-#### Inspection requested via web by kendall bender 250.53(A)(3)- Water piping system used for grounding electrode shall have supplemental rod. 334.12(B)(4)- NM cable shall not be install in a damp or wet location. Whip from disc to AC. 200.7(C)- If white conductor is used for other than grounded conductor it shall be re-identified other than white. Verbal with contact
|
Issue PAID IN FULL permit | | | 7/7/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/7/2015 | | DONE |
|
|
|
This permit was created on the web by kendall bender
|