Final | 8/17/2015 | 8/17/2015 | 8/17/2015 | P | PASS |
Rex Boyles
|
|
|
Good morning. This will be a final for this project please. Contact is David Forbes ###-####. Please call David if you have any questions as he will not be on this job site today. Thank you and have a super day! Phone #: ###-#### Inspection requested via web by Laura Longshaw corrections made final ok
|
Final | 7/30/2015 | 8/4/2015 | 8/4/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Final inspection for this property please. Contact will be Justin Metcalf ###-####. Please call ahead of arrival as he will not be on site. Thank you so much and have a wonderful day! Phone #: ###-#### Inspection requested via web by Laura Longshaw Finished work from permit ELE15-00532. 210.8- GFCI shall be located in a readily accessible location. Island GFCI. 210.52(C)(5)- Kitchen counter top receptacle outlets shall not be located more than 20" above counter top. 210.52(C)(5)ex.- Island counter top receptacle outlet shall not be located more than 6" under over hang. 680.22(A)(2)2- Pool circulating pump shall have GFCI protection. 680.22(B)- Pool luminaire shall have GFCI protection. 680.26(B)(7)- Pool equipment shall be bonded with a #8 solid conductor. pump motor.
|
Issue PAID IN FULL permit | | | 7/7/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/7/2015 | | DONE |
|
|
|
This permit was created on the web by Laura Longshaw
|