DOC - Permit Expired | 2/5/2019 | 2/5/2019 | 2/5/2019 | P | PASS |
Daryl DeGrange
|
|
|
No activity within 180 days. This permit is EXPIRED. A new permit is required to complete this job.
|
Permanent Service | 7/27/2015 | 7/27/2015 | 7/27/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Becky// please call for access Phone #: ###-#### BCC 4-05-32- Code violation not to be retained. BCC 4-05-31(C)- Unfused conductors shall not enter structure. NEC 230.70- A means shall be provided to disconnect all conductors in a building from the service entrance conductors. NEC 250.53(a)(2)- Underground metal water pipe used as grounding electode shall have a supplemental rod installed. NEC 110.3(A)- Neutral branch circuit conductor shows evidence of arcing in panel. Must have electrical contractor make corrections.
|
Final | 7/20/2015 | 7/20/2015 | 7/20/2015 | P | NH |
Rock A. Hudson
|
|
|
Becki Phone #: ###-#### Number provided not allacated. Unable to reach contact for access
|
Application received | | | 7/20/2015 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 7/20/2015 | | DONE |
|
|
|
|