DOC - Permit Expired | 2/5/2019 | 2/5/2019 | 2/5/2019 | P | PASS |
Daryl DeGrange
|
|
|
No activity within 180 days. This permit is EXPIRED. A new permit is required to complete this job.
|
Final | 12/14/2016 | 12/14/2016 | 12/14/2016 | P | PART |
James Ady
|
|
|
Home owner is home today. Go in front door Phone #: ###-#### Inspection requested via web by mike brown Receps needed behind sink as per 210.52C1 partial final ok
|
Electrical Rough-In | 5/11/2016 | 5/12/2016 | 5/12/2016 | A | PASS |
James Ady
|
|
|
Floor heat. Front door open. Upstairs bathroom Phone #: ###-#### Inspection requested via web by mike brown Up bath floor heat ok to cover
|
Electrical Rough-In | 5/11/2016 | 5/11/2016 | 5/11/2016 | P | CANC |
Rock A. Hudson
|
|
|
Floor heat. Use front door Phone #: ###-#### >> Inspection requested via web by mike brown Inspection cancelled from web by: mike brown
|
Permanent Service | 12/10/2015 | 12/11/2015 | 12/11/2015 | P | PASS |
Rock A. Hudson
|
|
|
this is a service change. please call for schedule to inspect once service is complete Phone #: ###-#### Inspection requested via web by mike brown p/s u/g rec ok
|
Electrical Rough-In | 10/16/2015 | 10/16/2015 | 10/16/2015 | A | PASS |
Rock A. Hudson
|
|
|
master bedroom and bathroom only. front door will be open. no one living on site at this time Phone #: ###-#### Inspection requested via web by mike brown Rough in ok cover
|
Electrical Rough-In | 9/28/2015 | 9/28/2015 | 9/28/2015 | P | PASS |
Rock A. Hudson
|
|
|
READY ANYTIME TODAY Phone #: ###-#### Inspection requested via web by mike brown Kitchen, outdoor enclosed patio rough in ok cover
|
Conference | 9/24/2015 | 9/25/2015 | 9/24/2015 | A | DONE |
Rock A. Hudson
|
|
|
Ready now Inspection requested via web by mike brown Discussed with contractor if receptacle outlets would be code required for counter top space behind kitchen sink. Counter top area behind sink is to be greater than 12" creating useable counter space. 2 receptacle outlets minimum behind sink required as per 210.52(C)(1)
|
Final | 7/24/2015 | 7/24/2015 | 7/24/2015 | P | CANC |
Rock A. Hudson
|
|
|
PLEASE CALL JON FOR ACCESS ###-#### Phone #: ###-#### Inspection requested via web by mike brown Needed Rough in inspection
|
Electrical Rough-In | 7/24/2015 | 7/24/2015 | 7/24/2015 | P | PART |
Rock A. Hudson
|
|
|
PLEASE CALL JON FOR ACCESS ###-#### Phone #: ###-#### Inspection requested via web by mike brown Discussed with general contractor enclosed patio would be considered a habitable room, BBQ area flat to window would be acceptable to have receptacle outlet at end of cabinet. Wall space only applys to walls and fixed panels on sliding windows. Basement rec room only rough in ok cover
|
Issue PAID IN FULL permit | | | 7/24/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/24/2015 | | DONE |
|
|
|
This permit was created on the web by mike brown
|