Final | 12/23/2015 | 12/24/2015 | 12/24/2015 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Lynn Cable owners moved in, could only do part of plug check, ok final, told to call floor heat in separate
|
Fees Due Hold | 10/22/2015 | | 10/26/2015 | | DONE |
|
|
|
|
Rough-In Permanent Service | 8/20/2015 | 8/20/2015 | 8/20/2015 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Lynn Cable corrections made r/i ok p/s u/g n ok
|
Electrical Rough-In | 8/20/2015 | 8/20/2015 | 8/20/2015 | P | CANC |
Rex Boyles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Lynn Cable Inspection cancelled from web by: Lynn Cable
|
Rough-In Permanent Service | 8/17/2015 | 8/18/2015 | 8/18/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Lynn Cable Family room NM cable not inside wall. nail plate behind furnace. Verbal with contractor
|
Electrical Rough-In | 8/5/2015 | 8/6/2015 | 8/6/2015 | A | PASS |
Rex Boyles
|
|
|
Cover inspection for Exterior porches and soffit cans. Also homeowner talked to Rex about looking at possible panel locations Phone #: ###-#### Inspection requested via web by Lynn Cable r/i soffits ok to cover NOTE:clearance issues above and in front of desired loadcenter location in mechanical room as per 2014 NEC 110.26(A)(2) and (3) and 110.26(E)(1)(a)-no piping or ductwork shall be located in this zone(dedicated equipment space)
|
Issue PAID IN FULL permit | | | 8/5/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/5/2015 | | DONE |
|
|
|
This permit was created on the web by Lynn Cable
|