Final | 12/3/2015 | 12/4/2015 | 12/4/2015 | A | PASS |
Rock A. Hudson
|
|
|
Lockbox 1976, thank you. Phone #: ###-#### Inspection requested via web by Clay Morgan Final ok
|
Final | 12/1/2015 | 12/2/2015 | 12/2/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Garage Code 5248. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan 210.52(C)(4)- If area behind sink is 12" or greater deep sink does not seperate counter space. Receptacle outlet required behind sink. 330.30(B)- MC ran to peninsula box shall be secured with in 12" of box. 408.4- Circuit directory shall accurately identify branch circuits and main. Lock box code is 1976
|
Rough-In Permanent Service | 8/18/2015 | 8/19/2015 | 8/19/2015 | A | PASS |
Rock A. Hudson
|
|
|
If you have any questions, please call Aaron at ###-#### for access info. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan Rough in ok cover p/s u/g rec ok
|
Issue PAID IN FULL permit | | | 8/7/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/7/2015 | | DONE |
|
|
|
This permit was created on the web by Clay Morgan
|