Final | 9/22/2015 | 9/23/2015 | 9/23/2015 | A | PASS |
Rex Boyles
|
|
|
call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson final ok David is going to install gfci receptacle behind washer and gfci on drinking fountain even though no work was done in these areas
|
Electrical Rough-In | 8/19/2015 | 8/19/2015 | 8/19/2015 | P | PASS |
Rex Boyles
|
|
|
call ###-#### for access, It is our understanding that no medical equipment will be in tenant rooms, therefore, no redundant ground will be required Phone #: ###-#### Inspection requested via web by David Nelson r/i ok (no redundant ground neccessary)
|
Electrical Rough-In | 8/11/2015 | 8/12/2015 | 8/12/2015 | A | NR |
Rex Boyles
|
|
|
call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson discussed electric requirements in "birthing rooms" considered "wet procedure location" in NEC 517.18 shall have redundant ground system. not ready for r/i at this time.
|
Issue PAID IN FULL permit | | | 8/11/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/11/2015 | | DONE |
|
|
|
This permit was created on the web by David Nelson
|