Final | 12/29/2015 | 12/29/2015 | 12/29/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson No card posted. ETL listing on over chair luminaires. Final ok
|
Final | 12/28/2015 | 12/29/2015 | 12/29/2015 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson corrections not made, called, lights over patient chair not listed, gfci not working in south patient area, can't reset gfci in bath, will fix and recall
|
Final | 12/28/2015 | 12/28/2015 | 12/28/2015 | P | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson equipment listed, floor boxes fed with proper wiring. BUT 517.18(B)- all receptacles in procedure rooms shall be listed "hospital grade" and shall be so identified. 110.16-Arc flash warning label required on loadcenters. Update panel schedule
|
Final | 12/23/2015 | 12/24/2015 | 12/24/2015 | A | NR |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson called, covers off plugs and switches, shall show listings for equipment, check on hospital grade receptacles with 327
|
Electrical Rough-In | 10/7/2015 | 10/8/2015 | 10/8/2015 | P | PASS |
Rock A. Hudson
|
|
|
Rough for 4 dental stations Phone #: ###-#### Inspection requested via web by Zane Robertson Floor receptacle outlets fed with ENT. Made note on correction from previous inspection to remove power cords that have been fished down interior wall and to refeed floor boxes for dental chairs with an approved method. Walls and patches rough in ok cover
|
Electrical Rough-In | 9/21/2015 | 9/21/2015 | 9/21/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Electrical rough in for relocated walls Phone #: ###-#### Inspection requested via web by Zane Robertson 400.8(2)- Flexible cords shall not be ran through holes in walls. 517.13- Branch circuits serving patient care areas shall be provided with and effective ground fault path by installation in a metal raceway system, or cable having a metal armor or sheath assembly.
|
Issue PAID IN FULL permit | | | 8/19/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/19/2015 | | DONE |
|
|
|
This permit was created on the web by Zane Robertson
|
First Notice | 12/29/2015 | 12/29/2015 | | | |
Rock A. Hudson
|
|
|
|