Final | 10/14/2015 | 10/14/2015 | 10/14/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson Final ok
|
Final | 10/9/2015 | 10/12/2015 | 10/12/2015 | A | FAIL |
Rock A. Hudson
|
|
|
call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson 110.26- work space for panel in pantry shall have a minimum of 30" wide floor to ceiling. BCC 4-05-32- No violation shall be retained. 314.20- Boxes located in walls with wood panels shall have a spark ring installed. 210.8- Receptacle outlets located with in 6' of a sink shall have GFCI protection. 314.23(A)- Meter enclosure shall be securely mounted in place. 334.30- NM cable in island shall be secured in place
|
Electrical Rough-In | 8/21/2015 | 8/24/2015 | 8/24/2015 | A | PASS |
Rock A. Hudson
|
|
|
call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson kitchen area replaced lighting and panel due to fire. Secure meter/main for final. Rough in ok cover
|
Issue PAID IN FULL permit | | | 8/21/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/21/2015 | | DONE |
|
|
|
This permit was created on the web by David Nelson
|