Final | 10/27/2015 | 10/28/2015 | 10/28/2015 | P | PASS |
Rex Boyles
|
|
|
FOR QUESTIONS PLEASE CONTACT ELECTRICIAN BEN- ###-#### Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON corrections made final ok perm. occupancy ok
|
Final | 10/23/2015 | 10/27/2015 | 10/27/2015 | P | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON remove abandoned conduit and wiring 408.7-filler plates required in unused openings of panel. 110.16-Arc flash warning labels required on all panels. 300.15-Remove abandoned conduit and wire. 330.30- MC type cable shall be secured and supported within 12" of enclosure and every 6' thereafter. 408.4(A)- circuit directory required for loads served in panels. Ceilings tiles installed prior to inspection need to be removed.
|
Final | 10/22/2015 | 10/23/2015 | 10/23/2015 | P | NR |
Rex Boyles
|
|
|
FOR ACCESS TO SECOND FLOOR USE CODE 4705# AND THEN CHOOSE 2ND FLOOR IN ELEVATOR....... INSPECTION IS FOR CEILING AND NEW OFFICE AREA... WITH ANY QUESTIONS PLEASE CONTACT ELECTRICIAN, BEN ###-#### Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON support cables up off ceiling grid, no power to cubicles, need access to electrical rm.
|
Electrical Rough-In | 9/30/2015 | 10/1/2015 | 10/1/2015 | A | PASS |
Rex Boyles
|
|
|
ELEVATOR CODE TO SECOND FLOOR 4705# Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON r/i walls ok northwest offices (SUITE 225)
|
Electrical Rough-In | 8/26/2015 | 8/27/2015 | 8/27/2015 | A | PASS |
Rex Boyles
|
|
|
THE WIRING NEEDING INSPECTION IS ON THE SECOND FLOOR OF PARK PLAZA BUILDING. ONE SIDE OF THE WALL IS OPEN AND THE OTHER SIDE IS CLOSED. IF YOU NEED HELP FINDING THESE WALLS PLEASE CONTACT THE ELECTRICIAN BEN AT ###-#### THANKS Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON r/i walls ok
|
Issue PAID IN FULL permit | | | 8/26/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/26/2015 | | DONE |
|
|
|
This permit was created on the web by SHAWN TOMLINSON
|
First Notice | 10/28/2015 | 10/28/2015 | | | |
Rex Boyles
|
|
|
|