Final | 3/10/2016 | 3/17/2016 | 3/17/2016 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Brandon Hillman final ok
|
Final | 3/11/2016 | 3/11/2016 | 3/11/2016 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Brandon Hillman corrections fixed final ok
|
Final | 3/4/2016 | 3/4/2016 | 3/4/2016 | P | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Brandon Hillman 408.4 circuit directory shall be indentified 210.8(a)(2) garage receptacles shall have GFCI protection 210.8(a)(3) outdoor receptacles shall have GFCI protection 210.8(a)(6) kitchen receptacles shall have GFCI protection(cant verify it nor locate the GFCI 406.5 receptacle mounting shall be secured(few are loose in laundry) entry recept and out light in-op
|
Rough-In Permanent Service | 11/1/2015 | 11/2/2015 | 11/2/2015 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Brandon Hillman rough-in ok cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 8/27/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/27/2015 | | DONE |
|
|
|
This permit was created on the web by Brandon Hillman
|