Final | 9/16/2015 | 9/16/2015 | 9/16/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Final ok
|
Final | 9/15/2015 | 9/15/2015 | 9/15/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack 408.4- Circuit directory shall be complete. 430.101- A lockable disconnecting means shall be installed between source and controller. 110.25- lock out acceptable
|
Permanent Service | 8/28/2015 | 8/31/2015 | 8/31/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack p/s u/g n ok
|
Issue PAID IN FULL permit | | | 8/28/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/28/2015 | | DONE |
|
|
|
This permit was created on the web by Lee VanSchoiack
|