Final | 1/20/2016 | 1/20/2016 | 1/20/2016 | P | PASS |
Bob Reichert
|
|
|
Garage code 3066. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov corrections made, ok final
|
Final | 1/18/2016 | 1/19/2016 | 1/19/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 210.52- Receptacle needed right side of butlers counter space. 110.3- Recptacle below iron not working. Corrections not complete
|
Final | 1/14/2016 | 1/14/2016 | 1/14/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 110.3- Receptacles shall be connected as per instructions. GFCI below iron tripped but would not reset. 210.8(A)(2)- All 15 and 20 amp receptacle outlets located in garage shall have GFCI protection. 210.8(A)(6)- All receptacle outlets serving counter top in kitchen areas shall have GFCI protection. Butlers pantry. 210.52(C)- A receptacle outlet shall be located with in 24" of right side of counter in butlers pantry.
|
Rough-In Permanent Service | 8/31/2015 | 9/1/2015 | 9/1/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 8/31/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/31/2015 | | DONE |
|
|
|
This permit was created on the web by daniel bibikov
|