Final | 11/24/2015 | 11/25/2015 | 11/25/2015 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams house panel and branch circuits final ok perm. occupancy ok
|
Permanent Service | 11/13/2015 | 11/13/2015 | 11/13/2015 | P | PASS |
Rex Boyles
|
|
|
on meter p/s u/g n ok pedestal for St lukes maint. shop (135 warm springs ave)
|
Override - Parcel Holds | | | 11/13/2015 | | |
|
|
|
|
Final | 11/9/2015 | 11/9/2015 | 11/9/2015 | P | FAIL |
Rex Boyles
|
|
|
Pedestal meter Phone #: ###-#### Inspection requested via web by Jim Williams 110.24(A)-Service equipment in other than dwelling units shall be legibly marked in the field with the maximum available fault current. 110.16 electrical equipment in other than dwellings shall be marked with arc flash warning label. Please put new address for new tenant (ST. Lukes) Please call for "perm. service" when ready
|
Final | 10/29/2015 | 10/29/2015 | 10/29/2015 | P | CANC |
Rex Boyles
|
|
|
House panel Phone #: ###-#### Inspection requested via web by Jim Williams needed p/s
|
Permanent Service | 10/29/2015 | 10/29/2015 | 10/29/2015 | P | PASS |
Rex Boyles
|
|
|
House panel Phone #: ###-#### Inspection requested via web by Jim Williams p/s ug n ok 100amp house panel meter
|
Electrical Rough-In | 10/27/2015 | 10/28/2015 | 10/28/2015 | A | PASS |
Rex Boyles
|
|
|
2 bathrooms Phone #: ###-#### Inspection requested via web by Jim Williams r/i 2 bath walls and hard lids ok
|
Permanent Service | 10/21/2015 | 10/21/2015 | 10/21/2015 | A | NR |
Rex Boyles
|
|
|
Suite 100 panel Phone #: ###-#### Inspection requested via web by Jim Williams not ready walls not framed yet for house panel install
|
Permanent Service | 10/14/2015 | 10/15/2015 | 10/15/2015 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams p/s u/g n ok
|
Conference | 10/12/2015 | 10/13/2015 | 10/13/2015 | A | DONE |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams discuss bonding and grounding electrode conductor for new service for 111 and 139. Asked Jim to drive 2 ground rods at each service and bond fire sprinkeler risers and sections of copper plumbing piping nearest service. OK to bring grounding electrode conductors into termination cabinet with nuetral disconnect link installed by factory.
|
Electrical Rough-In | 9/10/2015 | 9/10/2015 | 9/10/2015 | P | PASS |
Bob Reichert
|
|
|
Ext. wall lights Phone #: ###-#### Inspection requested via web by Jim Williams ok cover exterior lights
|
Issue PAID IN FULL permit | | | 9/10/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/4/2015 | | DONE |
|
|
|
This permit was created on the web by Jim Williams
|
First Notice | 11/25/2015 | 11/25/2015 | | | |
Rex Boyles
|
|
|
|