Final | 3/3/2016 | 3/4/2016 | 3/4/2016 | A | PASS |
Rex Boyles
|
|
|
Semir Phone #: ###-#### corrections made final ok
|
Final | 2/25/2016 | 2/26/2016 | 2/26/2016 | A | NR |
Rex Boyles
|
|
|
Semir Phone #: ###-#### Both GFCI receptacles also need to be tamper resistant
|
Final | 2/17/2016 | 2/19/2016 | 2/19/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Semir Phone #: ###-#### 210.8- All receptacle outlets serving kitchen counter top areas shall have GFCI protection. 406.12(A)- All new 15 and 20 amp 120 volt receptacle outlets shall be tamper resistant type. Called and left message
|
Electrical Rough-In | 9/22/2015 | 9/23/2015 | 9/23/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Very nice work no conference needed. M. bath, new closet, kitchen remodel, new utility room rough in ok cover
|
Issue PAID IN FULL permit | | | 9/4/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Issue PAID IN FULL permit | | | 9/4/2015 | | DONE |
|
|
|
|
Application received | | | 9/4/2015 | | |
|
|
|
|