Final | 11/2/2016 | 11/3/2016 | 11/3/2016 | A | PASS |
Eric Story
|
|
|
Juile Phone #: ###-#### correction fixed final ok
|
Final | 11/1/2016 | 11/2/2016 | 11/2/2016 | A | FAIL |
Eric Story
|
|
|
Juile Phone #: ###-#### 210.8 all exterior receptacles shall be GFCI protected 406.6 Faceplates required 496.4(5) tamper resistant receptacles required
|
Electrical Rough-In | 9/10/2015 | 9/11/2015 | 9/11/2015 | A | PASS |
Rex Boyles
|
|
|
Juile Phone #: ###-#### corrections made r/i ok will call for another r/i at south patio door when ready
|
Electrical Rough-In | 9/8/2015 | 9/10/2015 | 9/10/2015 | A | DONE |
Rex Boyles
|
|
|
Change day per Julie Phone #: ###-#### Note: Owyhee STREET conference and partial r/i inspection. Make up grounds. NEC 334.30 secure and staple nm cable 12" from box and every 4'6" thereafter. Install flexable raceway around thhn conductors. NEC 250.8-ground screws required in metal boxes
|
Application received | | | 9/8/2015 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 9/8/2015 | | DONE |
|
|
|
|