Final | 11/19/2015 | 11/19/2015 | 11/19/2015 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Brad Girard corrections made final ok
|
Final | 11/18/2015 | 11/18/2015 | 11/18/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Brad Girard 110.3- Receptacle shall be wired to manufacturers instructions. Open ground in master bed. ' 342.30- IMC overhead service riser shall be secured with in 3' of meter base. 406.12- All receptacle outlets installed in a residence shall be tamper resistant type. Garage GFI
|
Rough-In Permanent Service | 9/21/2015 | 9/21/2015 | 9/21/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Brad Girard Full house rough in ok cover p/s o/h rec ok
|
Rough-In Permanent Service | 9/18/2015 | 9/18/2015 | 9/18/2015 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Brad Girard Additional switch leg is needed for ceiling fans, additional receptacle in first hall bedroom, bond incoming metal water pipe within first 5 ft.
|
Issue PAID IN FULL permit | | | 9/16/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/16/2015 | | DONE |
|
|
|
This permit was created on the web by Brad Girard
|