Final | 1/6/2016 | 1/7/2016 | 1/7/2016 | A | PASS |
Eric Story
|
|
|
lock box 1049 Phone #: ###-#### Inspection requested via web by Neal Rumsey as per rex boyles final ok
|
Final | 1/4/2016 | 1/5/2016 | 1/5/2016 | A | FAIL |
Rex Boyles
|
|
|
Lock box code 1049 Phone #: ###-#### Inspection requested via web by Neal Rumsey Dining room receptacle has open ground, 210.12(A) and (B)-all outlets in bedrooms shall be AFCI protected, 250.52(A)(1)- metal underground water pipe shall be bonded to service, 422.31(B)-water heater shall have disconnect in sight or lockoff on breaker, 210.63- a 120 volt receptacle shall be installed within 25 foot of HVAC equipment
|
Rough-In Permanent Service | 10/12/2015 | 10/12/2015 | 10/12/2015 | P | PASS |
Rex Boyles
|
|
|
Code 1049 Phone #: ###-#### Inspection requested via web by Neal Rumsey r/i ok p/s o/h n ok
|
Issue PAID IN FULL permit | | | 9/21/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/21/2015 | | DONE |
|
|
|
This permit was created on the web by Neal Rumsey
|