First Notice | 3/10/2016 | 3/10/2016 | 3/14/2016 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Debby Pierce
|
Final | 3/9/2016 | 3/10/2016 | 3/10/2016 | A | PASS |
Rock A. Hudson
|
|
|
Greg Milburn is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Value of ELE permit covers total shell and TI. Asked contractor to call and pull permit for TI, assign to TI BLD, and request inspection for TI final. TI and core and shell tested ok. Final ok
|
Final | 3/7/2016 | 3/7/2016 | 3/7/2016 | P | FAIL |
Eric Story
|
|
|
Please contact Greg Milburn at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce 440.22 protective device rating shall not exceed manufactures rating
|
Electrical Rough-In | 3/2/2016 | 3/2/2016 | 3/2/2016 | P | PASS |
Rock A. Hudson
|
|
|
ceiling Inspection, Greg Millburn is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Grid complete. Rough in ok cover
|
Electrical Rough-In | 2/16/2016 | 2/17/2016 | 2/17/2016 | A | PASS |
Rock A. Hudson
|
|
|
ceiling Inspection, Greg Milburn is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce couple fixtures damaged in shipping contractor to leave grid open where missing are located. Grid rough in ok cover
|
Electrical Rough-In | 12/30/2015 | 12/30/2015 | 12/30/2015 | P | CANC |
Rock A. Hudson
|
|
|
service inspection, Greg Milburn is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Needed permanent service inspection
|
Permanent Service | 12/30/2015 | 12/30/2015 | 12/30/2015 | P | PASS |
Rock A. Hudson
|
|
|
service inspection, Greg Milburn is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce p/s u/g n ok
|
Electrical Rough-In | 12/28/2015 | 12/28/2015 | 12/28/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Service Inspection?? Greg Milburn is contact at ###-####-. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Confirmed 3/0 concrete encased electrode termination and 65K rated mains. 110.24- Available fault current shall be posted with date calculated prior to permanent service inspection.
|
Electrical Rough-In | 12/17/2015 | 12/18/2015 | 12/18/2015 | P | PASS |
Rock A. Hudson
|
|
|
Greg Milburn is contact at ###-####, rough in Lobby... Phone #: ###-#### Inspection requested via web by Debby Pierce Lobby walls and hardlid rough in ok cover
|
Electrical Rough-In | 12/14/2015 | 12/15/2015 | 12/15/2015 | A | PASS |
Rock A. Hudson
|
|
|
Greg Milburn is contact ###-####.. thank you.. Phone #: ###-#### Inspection requested via web by Debby Pierce Walls except foyer rough in ok cover
|
Electrical Rough-In | 12/1/2015 | 12/1/2015 | 12/1/2015 | P | PASS |
Rock A. Hudson
|
|
|
Ceiling Inspection, hard lid. Greg Milburn is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce 2 conference rooms and IT room hardlids only rough in ok cover
|
Electrical Rough-In | 10/8/2015 | 10/8/2015 | 10/8/2015 | P | PASS |
Rock A. Hudson
|
|
|
UNDERGROUND Inspection, please. Chad Van Orden is contact at ###-####. thank you Phone #: ###-#### Inspection requested via web by Debby Pierce Underslab low volt and 2 stub each side of entrance rough in ok cover
|
Electrical Rough-In | 10/5/2015 | 10/5/2015 | 10/5/2015 | P | PASS |
Rock A. Hudson
|
|
|
Underground Inspection. contact is Chad VanOrden at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Feeders and stubs through foundation rough in ok cover
|
Electrical Rough-In | 9/29/2015 | 9/30/2015 | 9/30/2015 | A | PASS |
Rock A. Hudson
|
|
|
Grounding Inspection, Chad Van Orden is contact. ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Concrete encased electrode rough in ok cover
|
Issue PAID IN FULL permit | | | 9/29/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 9/29/2015 | | |
|
|
|
|
Application received | | | 9/29/2015 | | DONE |
|
|
|
This permit was created on the web by Debby Pierce
|