First Notice | 10/22/2015 | 10/22/2015 | 10/30/2015 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Clint Tate
|
Final | 10/21/2015 | 10/22/2015 | 10/22/2015 | A | PASS |
Rock A. Hudson
|
|
|
We are requesting a final inspection on this project for tomorrow in the AM. Our contact is Kory @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate Questioned location of GFCI receptacles. Contractor stated all equipment will be on counter tops so GFCI receptacles all readily accessible at time of final. Final ok
|
Final | 10/20/2015 | 10/21/2015 | 10/21/2015 | A | FAIL |
Rock A. Hudson
|
|
|
We are requesting a final inspection for tomorrow 10/21/15. Our contact for this is Kory @###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate 210.8(B)(2)- All 120 volt 15 and 20 amp receptacle outlets located in commercial kitchens shall have GFCI protection. 406.6- Receptacle faceplates shall be installed to completely cover opening. 240 volt under counter to right of registers.
|
Electrical Rough-In | 10/13/2015 | 10/14/2015 | 10/14/2015 | A | PASS |
Rock A. Hudson
|
|
|
We are requesting a ceiling inspection for tomorrow 10/14/15 in the AM. Our contact is Kory @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Check flexible cords for power supply located above grid above 4' track to west have been removed on final. Grid rough in ok cover
|
Electrical Rough-In | 9/29/2015 | 9/29/2015 | 9/29/2015 | P | PASS |
Rock A. Hudson
|
|
|
We are requesting a wall rough-in inspection for today 9/29/15 in the afternoon. Our contact is Kory @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate Walls and hardlid rough in ok cover
|
Issue PAID IN FULL permit | | | 9/29/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/29/2015 | | DONE |
|
|
|
This permit was created on the web by Clint Tate
|