Final | 10/27/2015 | 10/27/2015 | 10/27/2015 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams corrections made area classification changed to regular garage. final ok
|
Final | 10/22/2015 | 10/23/2015 | 10/23/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams 408.37- Panelboard installed outdoors in damp location shall have cover to prevent moisture from entering. 547.6- Receptacle outlets shall have enclosure to prevent entry of dust. 547.7- Motor for garage door opener shall be totally enlosed to prevint dust entry. 547.8- Luminaires in hay storage area shall be type to prevent entry of dust.
|
Electrical Rough-In | 9/30/2015 | 10/1/2015 | 9/30/2015 | A | CANC |
Rex Boyles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Jim Williams Inspection cancelled from web by: Jim Williams
|
Electrical Rough-In | 9/29/2015 | 9/30/2015 | 9/30/2015 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams r/i ok left message for Jim to remove bonding screw in sub panel and expose underground to barn for inspection of subfeed
|
Issue PAID IN FULL permit | | | 9/29/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/29/2015 | | DONE |
|
|
|
This permit was created on the web by Jim Williams
|