Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE15-03137
StatusFinaled
Name CAPITOL ELECTRIC
Site Address 2123 S EAGLESON RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: Wiring for barn
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/27/201510/27/201510/27/2015APASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by Jim Williams corrections made area classification changed to regular garage. final ok
Final10/22/201510/23/201510/23/2015AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jim Williams
408.37- Panelboard installed outdoors in damp location shall have cover to prevent moisture from entering.
547.6- Receptacle outlets shall have enclosure to prevent entry of dust.
547.7- Motor for garage door opener shall be totally enlosed to prevint dust entry.
547.8- Luminaires in hay storage area shall be type to prevent entry of dust.
Electrical Rough-In9/30/201510/1/20159/30/2015ACANC
DetailsRex Boyles
Phone #: ###-#### >> Inspection requested via web by Jim Williams Inspection cancelled from web by: Jim Williams
Electrical Rough-In9/29/20159/30/20159/30/2015APASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by Jim Williams r/i ok left message for Jim to remove bonding screw in sub panel and expose underground to barn for inspection of subfeed
Issue PAID IN FULL permit  9/29/2015 DONE
Payment received via Govolutions
Application received  9/29/2015 DONE
This permit was created on the web by Jim Williams