First Notice | 10/9/2015 | 10/9/2015 | 10/9/2015 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Stacie Tasker
|
First Notice | 10/9/2015 | 10/9/2015 | 10/9/2015 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Stacie Tasker
|
Temporary Service | 10/9/2015 | 10/9/2015 | 10/9/2015 | P | PASS |
Rock A. Hudson
|
|
|
t/s u/g n ok
|
Final | 10/8/2015 | 10/9/2015 | 10/9/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Stacie Tasker t/s u/g n ok
|
Final | 10/6/2015 | 10/6/2015 | 10/6/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Please call ahead of time, Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker 350.12(1)- LFMC shall not be installed wher subject to physical damage. 300.5(D)(4)- Shere conductors emerge from grade they are concidered subject to physical damage and shall be protected by heavy wall conduit, rigid, IMC, or SCH 80 PVC. 590.6(B)- Use of other outlets. Temp power used for construction shall have GFCI protection.
|
Issue PAID IN FULL permit | | | 10/5/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/5/2015 | | DONE |
|
|
|
This permit was created on the web by Stacie Tasker
|