Final | 11/25/2015 | 11/27/2015 | 11/27/2015 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn correction done, final ok
|
Final | 11/24/2015 | 11/25/2015 | 11/25/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 250.94- Intersystem bond termination shall be provided for other systems
|
Permanent Service | 11/13/2015 | 11/16/2015 | 11/16/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn p/s u/g n ok
|
Rough-In Permanent Service | 10/19/2015 | 10/20/2015 | 10/20/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 310.15(B)(7)(1)- Service entrance conductors. 200a x .83=166amps, 75 degree only, 2/0 minimum shall be used.
|
Electrical Rough-In | 10/20/2015 | 10/20/2015 | 10/20/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn House only rough in ok cover.
|
Issue PAID IN FULL permit | | | 10/19/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/19/2015 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|