First Notice | 5/26/2016 | 5/26/2016 | 7/8/2016 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Stacie Tasker
|
Final | 5/26/2016 | 5/26/2016 | 5/26/2016 | P | PASS |
Rock A. Hudson
|
|
|
Contact is Tom. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Final ok
|
Final | 5/24/2016 | 5/25/2016 | 5/25/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Contact will be Tom. Thank you! Phone #: ###-#### Inspection requested via web by Stacie t 110.3(B)- Exhaust fan located in shower stall shall have GFCI protection as per manufacturers instructions. 210.8(A)(1)- All 120 volt receptacle outlets located in bathroom area shall have GFCI protection. washer. GFCI device shall be located in a readily accessible location. 210.12- All 120 volt outlets located in bedroom areas shall have AFCI protection. Smokes and closet switch. 406.12- All receptacle outlets 15 or 20 amp 120 volt shall be tamper resistant type if installed in or on a dwelling unit. Called contact, no answer, voicemail not set up yet. Left correction notice.
|
Electrical Rough-In | 11/23/2015 | 11/25/2015 | 11/25/2015 | A | CANC |
Rex Boyles
|
|
|
Travis Watson is our site contact, he can be reached at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker needed r/i and p/s
|
Rough-In Permanent Service | 11/25/2015 | 11/25/2015 | 11/25/2015 | P | PASS |
Rex Boyles
|
|
|
Travis Watson is our site contact, he can be reached at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker p/s o/h n ok r/i ok (will add nailplates and finish terminating mc in bathroom)
|
Electrical Rough-In | 10/20/2015 | 10/20/2015 | 10/20/2015 | P | PASS |
Rex Boyles
|
|
|
We need a Ufer inspection for today. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker r/i ok ufer
|
Issue PAID IN FULL permit | | | 10/20/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/20/2015 | | DONE |
|
|
|
This permit was created on the web by Stacie Tasker
|