Final | 11/6/2015 | 11/9/2015 | 11/9/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Bryan McLaughlin Final ok
|
Final | 11/5/2015 | 11/6/2015 | 11/6/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Bryan McLaughlin 300.11- All cables shall be supported independant of grid. Flex in niche, 12' fixture whip. 300.15- All cables shall terminate in a box. MC above water heater. 314.25- All boxes shall have covers. 404.9- All switches shall have cover to totally enclose switch.
|
Electrical Rough-In | 10/25/2015 | 10/26/2015 | 10/26/2015 | P | PASS |
Rock A. Hudson
|
|
|
walls Phone #: ###-#### Inspection requested via web by Bryan McLaughlin Wall rough in ok cover
|
Issue PAID IN FULL permit | | | 10/23/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/23/2015 | | DONE |
|
|
|
This permit was created on the web by Bryan McLaughlin
|
First Notice | 11/9/2015 | 11/9/2015 | | | |
Rock A. Hudson
|
|
|
|