Final | 7/17/2016 | 7/18/2016 | 7/18/2016 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Corrections made final ok
|
Final | 7/13/2016 | 7/13/2016 | 7/13/2016 | P | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI 680.12 Disconnect shall be outside of 5ft from waters edge, Hot tub.c 680.34 Recepticle shall be outside of 6ft from waters edge. Hot tub. Pantry outlets dont work
|
Rough-In Permanent Service | 10/28/2015 | 10/28/2015 | 10/28/2015 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI rough-in ok cover soffit boxes are 2hr fire rated p/s u/g n ok
|
Rough-In Permanent Service | 10/27/2015 | 10/27/2015 | 10/27/2015 | P | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI 334.12 type nm cable shall be protected from physical damage
|
Issue PAID IN FULL permit | | | 10/27/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/27/2015 | | DONE |
|
|
|
This permit was created on the web by TOM BICANDI
|