First Notice | 11/25/2015 | 11/25/2015 | 12/8/2015 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Richard Montgomery
|
Final | 11/25/2015 | 11/25/2015 | 11/25/2015 | P | PASS |
Rock A. Hudson
|
|
|
Electrical final. Contact is Jay Sprik. Phone #: ###-#### Inspection requested via web by Richard Montgomery Quoted 4.1 air exchanges per hour. Final ok
|
Final | 11/13/2015 | 11/13/2015 | 11/13/2015 | P | CANC |
Rock A. Hudson
|
|
|
Stacy Phone #: ###-#### Needed permanent service inspection
|
Permanent Service | 11/13/2015 | 11/13/2015 | 11/13/2015 | P | PASS |
Rock A. Hudson
|
|
|
Stacy Phone #: ###-#### 300.5(G)- Wher raceway contain #4 or larger conductors insulating bushings shall be installed. Nipples to interior panels on meter side. Will check next trip.
|
Electrical Rough-In | 10/29/2015 | 10/29/2015 | 10/29/2015 | P | PASS |
Rock A. Hudson
|
|
|
Underground electrical from transformer to building. Phone #: ###-#### Inspection requested via web by Richard Montgomery As noted rough in ok cover
|
Electrical Rough-In | 10/27/2015 | 10/28/2015 | 10/28/2015 | P | PASS |
Rock A. Hudson
|
|
|
Rough inspect of walls and ceiling areas. Contact is Matt Malloy. Phone #: ###-#### Inspection requested via web by Richard Montgomery Repair area to be ventilated as per 511.3(C)(1)a- 4 air exchanges per hour with vent ducts to be installed with in 12" of floor. All walls and ceilings rough in ok cover.
|
Issue PAID IN FULL permit | | | 10/27/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/27/2015 | | DONE |
|
|
|
This permit was created on the web by Richard Montgomery
|