Print Statement | | | 5/24/2016 | | DONE |
|
|
|
|
First Notice | 12/29/2015 | 12/29/2015 | 4/20/2016 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Richard Montgomery
|
Final | 12/29/2015 | 12/29/2015 | 12/29/2015 | P | PASS |
Rock A. Hudson
|
|
|
Electrical final. Contact is Jay Sprik. Phone #: ###-#### Inspection requested via web by Richard Montgomery Final ok
|
Permanent Service | 11/24/2015 | 11/24/2015 | 11/24/2015 | P | PASS |
Rock A. Hudson
|
|
|
Re-inspection of electrical service. Contact is Jay Sprik. Phone #: ###-#### Inspection requested via web by Richard Montgomery p/s u/g n ok
|
Permanent Service | 11/20/2015 | 11/20/2015 | 11/20/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Service inspection only. Contact is Jay Sprik. Phone #: ###-#### Inspection requested via web by Richard Montgomery 110.24-Available fault current shall be posted with value and date calculated prior to permanent service inspection. 300.4(G)- Raceways containing #4 or larger conductors shall have bushings installed to protect conductors from physical damage.
|
Electrical Rough-In | 11/18/2015 | 11/19/2015 | 11/19/2015 | A | PASS |
Daryl DeGrange
|
|
|
Electrical rough. Contact is Jay Sprik. Phone #: ###-#### Inspection requested via web by Richard Montgomery rough-in ok cover
|
Electrical Rough-In | 10/27/2015 | 10/27/2015 | 10/27/2015 | P | PASS |
Rock A. Hudson
|
|
|
Underground inspection from transformer to building. Contact on job is Matt Malloy. Phone #: ###-#### Inspection requested via web by Richard Montgomery Underground as noted rough in ok cover
|
Issue PAID IN FULL permit | | | 10/27/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/27/2015 | | DONE |
|
|
|
This permit was created on the web by Richard Montgomery
|