Final | 8/5/2016 | 8/5/2016 | 8/5/2016 | P | PASS |
Rock A. Hudson
|
|
|
corrections have been made Phone #: ###-#### Inspection requested via web by Shaun Kirkman Final ok
|
Final | 8/2/2016 | 8/3/2016 | 8/3/2016 | A | FAIL |
Rock A. Hudson
|
|
|
garage code is 1234 please call if you have any questions. Thank you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman 110.22- Furnace disconnecting means shall be identified as to its purpose. 210.8- All 15 and 20 amp receptacle outlets shall have GFCI protection. 300.21- Openings around electrical penetrations shall be sealed with fire resistant materials. Garage warm wall. 440.22- AC max overcurrent 25 amp, 30 amp installed.
|
Rough-In Permanent Service | 10/28/2015 | 10/28/2015 | 10/28/2015 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Shaun Kirkman r/i ok p/s u/g n ok
|
Issue PAID IN FULL permit | | | 10/28/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/28/2015 | | DONE |
|
|
|
This permit was created on the web by Shaun Kirkman
|