Final | 5/10/2016 | 5/11/2016 | 5/11/2016 | A | PASS |
Bob Reichert
|
|
|
Don Phone #: ###-#### ok final, signed card
|
Fees Due Hold | 1/16/2016 | | 5/10/2016 | | DONE |
Christina Prado
|
|
|
|
Rough-In Permanent Service | 1/13/2016 | 1/13/2016 | 1/13/2016 | P | PASS |
Bob Reichert
|
|
|
corrections have been made corey is on site today Phone #: ###-#### Inspection requested via web by Don Lustig ri ok, p/s u/g n ok, 9 meters required
|
Electrical Rough-In | 1/13/2016 | 1/13/2016 | 1/13/2016 | P | PASS |
Bob Reichert
|
|
|
corrections have been made corey is on site today Phone #: ###-#### Inspection requested via web by Don Lustig 1st 8 units ri ok ne group apartments, bldg 3
|
Electrical Rough-In | 1/12/2016 | 1/12/2016 | 1/12/2016 | P | CANC |
Bob Reichert
|
|
|
rough in on the first building 8 units Phone #: ###-#### Inspection requested via web by Don Lustig see rip response
|
Rough-In Permanent Service | 1/12/2016 | 1/12/2016 | 1/12/2016 | P | NR |
Bob Reichert
|
|
|
rough in on the first building 8 units Phone #: ###-#### Inspection requested via web by Don Lustig met contractor, shall provide available fault current sticker at service, shall install balcony receptacles, shall protect attis access, shall not staple flat nm on edge, shall box bath fixtures, shall install boxes flush with combustible material, shall install nail plates, shall provide lights and switches under stairs,
|
Conference | 11/19/2015 | 11/19/2015 | 11/19/2015 | P | DONE |
Bob Reichert
|
|
|
we are requesting a consult on the wiring and circuitry preferences by Boise City. we are not usually residential wireman, so a consult at the begining of 40,000 sqft might be a good idea. Corey is on site for a visit. Phone #: ###-#### Inspection requested via web by Don Lustig talked about wiring apartments and code requirements
|
Issue PAID IN FULL permit | | | 10/28/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/28/2015 | | DONE |
|
|
|
This permit was created on the web by Don Lustig
|
First Notice | 5/11/2016 | 5/11/2016 | | | |
Bob Reichert
|
|
|
|