Final | 2/4/2016 | 2/4/2016 | 2/4/2016 | P | PASS |
Eric Story
|
|
|
Garage code 3283. Thanks Eric Phone #: ###-#### Inspection requested via web by daniel bibikov corrections fixed final ok
|
Final | 2/2/2016 | 2/3/2016 | 2/3/2016 | A | FAIL |
Eric Story
|
|
|
Garage code 3283. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov 210.8 all 120v receptacles ina garage shall have GFCI protection 334.15 type NM cable shall not be used where subject to physical damage 210.8 all 120v receptacles located within 6' of a sink shall have GFCI protection 406.4 weather resistant receptales required 410.16 luminaires ina closet shall be completley enclosed
|
Rough-In Permanent Service | 11/2/2015 | 11/2/2015 | 11/2/2015 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov confirmed 2hr fire rating as per wui rough-in ok cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 11/2/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/2/2015 | | DONE |
|
|
|
This permit was created on the web by daniel bibikov
|