Final | 2/17/2016 | 2/18/2016 | 2/18/2016 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: 6311362 >> Inspection requested via mobile web by Mike Final ok
|
Final | 2/16/2016 | 2/17/2016 | 2/17/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: 6311362 >> Inspection requested via mobile web by Mike Owner installed floor heat in baths on main floor and basement without having inspected. Not having removed but shall have GFCI protection as per NEC 210.8
|
Electrical Rough-In | 11/6/2015 | 11/6/2015 | 11/6/2015 | P | PASS |
Rock A. Hudson
|
|
|
Rough in ok cover
|
Electrical Rough-In | 11/5/2015 | 11/5/2015 | 11/5/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Michael Phone #: ###-#### 210.52- Shall have receptacle outlet located with in 24" of left side of range. 250.64(C)- Splice for grounding electode conductor shall be with irriversible connector listed. Wiring for smoke detectors shall be completed.
|
Electrical Rough-In | 11/4/2015 | 11/4/2015 | 11/4/2015 | P | CANC |
Eric Story
|
|
|
homeowner is out of town but cousion will meet you there. Jay ###-#### needed conference
|
Conference | 11/4/2015 | 11/4/2015 | 11/4/2015 | P | DONE |
Eric Story
|
|
|
homeowner is out of town but cousion will meet you there. Jay ###-#### met with owners cousin and discussed panel location in a fire wall, bringing panel up to code for grounding with 2 ground rods,and nailplating wires within 1 1/4" of framing member. Requested homeowner be onsite for rough-in inspection
|
Issue PAID IN FULL permit | | | 11/4/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/4/2015 | | |
|
|
|
homeowner called he did the work and went out of town.,
|